|
Protection by fuses
It is very common to employ the radial system shown
and to use a major or upstream fuse in the supply connection (PD4)
and minor or down-stream fuses in the individual load circuits (PD1,
2 and 3).

Clearly, each minor fuse must have the time/current
characteristic needed to protect its load circuit and a fault on
a particular load should only cause its associated minor fuse to
operate. The major or upstream fuse (PD4) will also carry the fault
current but it must not operate or be impaired.
For faults which cause relatively small currents to flow, the arcing
times, as proportions of the pre-arcing times, are small and consequently
discrimination can be predicted by comparing the time current curves
of the major and minor fuses. Provided that the curves for the minor
fuses are to the left of that for the major fuse, i.e. the minor
fuses operate more quickly, then discrimination should be obtained.
At higher fault current levels which will result in melting of the
minor fuse in less than 100 ms, the arcing time of the minor fuse
must be taken into account. This is done not by considering the
actual values of time, but by using the I2t values. The requirement
is that the pre-arcing I2t of the major fuse shall exceed the total
operating I2t of the minor fuse by a reasonable margin (say 40%).
An integrated system protected by fuselinks excel in this application,
giving minimum disruption in the system. The standardisation of
gG fuselink characteristics ensures that discrimination between
fuselinks can be achieved on a 1.6:1 ratio of current ratings for
most practical situations. The 1.6:1 ratio represents two steps
in the R10 series of ratings, i.e. a 100A (downstream) fuselink
will discriminate with a 160A (upstream) fuselink.
The particular case which arises when discrimination has to be achieved
between fuses on the two sides of a transformer, the effective transformation
ratio needs to be taken into account.
|